TECHNO-AC Success ATP434E [ATP-434E] Cable Locator and Acoustic Fault Detector. Based on receiver AP-027, EMD-247 sensor and acoustic sensor AD-227. Cable locator and acoustic fault detector Success ATP-434E is recommended for application in the following industries.
Brief description:
Storage of 31 signal level with a graph displayed
Visual indication of the signal on the display: scale, graphic and spectrum
Graphic visualization (moving chart) of sequence of measurements, max and min signal levels
Sound indication: natural and synthesized sound
Broadband mode: 0.05 to 8.6 kHz
Broadband (fault mode): 0.09 to 2.20 kHz
Min and max method of tracing
Light weight
Comfortable to wear for long terms
LCD display
Application:
Detection of energized cable lines underground up to 6 m depth by passive method.
Cable fault location by electromagnetic and acoustic methods (with high-voltage pulse transmitter, which is not included into the set).
Detection of insulation deterioration on cables by contact and non-contact methods.
Energized cable detection underground up to 6 m depth
Acoustic cable fault detection
AP-027 RECEIVER FAULT LOCATION:
Type of accepted signal: Continuous /pulse
Leak detection depth: Up to 3 meters
Frequencies of the receiver’s filter: Central frequency of quasi- resonant filter 50 to 60 Hz,100 to 450 Hz through 50 Hz, 120 to 540 Hz through 60 Hz, 512 Hz / 1024 Hz / 8192 Hz/ 33kHz
«Broadband», (operating mode): 0,05 to 8,6 kHz
Gain factor: 100 dB
Visual indication: Liquid-crystal display-symbols and meaning of the chosen modes and parameters; Animated (moving) scale of the output signal level; Digital value and animated (moving) scale of the output signal level; Graphic (moving diagram) of the output signal level - frequency content of the output signal level; Digital and graphic display of output signal levels kept in the «memory»
Sound indication: Headphones natural broadband or filtered signal; Headphones-synthesized sound. Frequency modulation; Built-in emitter - synthesized sound. Frequency modulation
Supply Voltage : 4 to 7 V. - alkaline batteries АА type 1,5 V (4 pcs.)
Time of continuous operation not less than: 20 hours
Operation temperature: -20°С to +50°С
Ingress protection rating: IP54
Dimensions: 220 × 102 × 42 (mm)
Weight of the electronic unit: 0,46 kg
CABLE LOCATION:
Cable & pipe detection depth: Up to 6 meters
Frequencies of the receiver: 50...60 Hz, 100 to 450 Hz. through 50 Hz, 120 to 540 Hz through 60 Hz, 512 Hz / 1024 Hz / 8192 Hz/ 33kHz
Gain: 100 dB
Cable & pipe detection accuracy: ±5% of utility depth