• Dwyer 641 [641-6] Air Velocity Transmitter 6 Inch Probe Length without Display

Dwyer 641 [641-6] Air Velocity Transmitter 6 Inch Probe Length without Display

Not yet rated Write a review
Dwyer Instruments
Rp.21.205.000
Availability:
2 - 4 WEEKS
Product Code:
641-6
Brand:
Dwyer Instruments
Update Terakhir:
19 Jun 2023
  • Free delivery

  • Money back guarantee

Share

Dwyer 641-6 Air Velocity Transmitter 6 Inch Probe Length without Display is the ideal instrument for monitoring air flow. This transmitter uses a heated mass flow sensor which allows for precise velocity measurements at various flow rates and temperatures. The 641's 16 field selectable ranges provides it the versatility to be selected for several air flow applications. The optional LED produces a complete, low-cost solution for local indication of air flow.

The Dwyer 6416 air velocity transmitter is ideal for application such as: exhaust stack flow monitoring, air control in drying processes, HVAC air velocity measurements, fan supply and exhaust tracking, clean room fresh air supply, ensuring proper lab hood exhaust flow rates, and others.

  • Part Number: 641-6
  • Probe Length: 6"
  • Display: Without display
  • For use with clean air and compatible, non-combustible gases
  • Accurate up to ±3%
  • 1.5 second response time
  • Process temperature limit: -40 to 212°F
  • Pressure limit: 100 psi (6.89 bar) maximum
  • Ranges to 15,000 FPM or 75 MPS
  • Optional bright LED display
  • Easy push button set-up
  • Compact housing
  • 4-20 mA output, isolated 24V source, 3 or 4-wire connection
  • Digital filter for signal damping
  • Screw terminal electrical connection
  • 1/2" male NPT process connection

  • Service: Clean air and compatible, non-combustible gases.
  • Accuracy: 3% FS process gas: 32 to 122°F (0 to 50°C); 4% FS process
  • Gas: -40 to 32°F & 122 to 212°F (-40 to 0°C & 50 to 100°C).
  • Response Time: Flow: 1.5 seconds to 95% of final value (output filter set to minimum).
  • Temperature Limits: Process: -40 to 212°F (-40 to 100°C); Ambient: 32 to 140°F (0 to 60°C).
  • Pressure Limit: 100 psi (6.89 bar) maximum.
  • Humidity Limit: Non-condensing.
  • Power requirements: 12 to 35 VDC, 10 to 16 VAC. 1.5A rating required on supply due to initial power surge drawn by transmitter.
  • Output signal: 4 to 20 mA, isolated 24V source, 3 or 4-wire connection.
  • Output Filter: Selectable 0.5 –15 (seconds).
  • Loop resistance: 600 Ω max.
  • Current consumption: 300 mA max.
  • Electrical connections: Screw terminal.
  • Process connections: 1/2˝ male NPT.
  • Enclosure rating: Designed to meet NEMA 4X (IP66) for non LED models only.
  • Mounting orientation: Unit not position sensitive. Probe must be aligned with airflow.
  • Weight: 12.6 oz (357.2 g).
  • Agency Approval: CE.
  • OPTIONAL DISPLAY Version: Display: 4-1/2 digit 1/2˝ red LED. Resolution: 1 FPM, 0.01 MPS (10 FPM @ 10,000 and 15,000 FPM ranges).
  • Weight: 13.3 oz (377 g).

  • (1) 6 Inch Probe Length
  • (1) Instruction Manual

Download