• AEMC 6472 [2135.51] 2-Point, 3-Point and 4-Point Digital Ground Resistance

AEMC 6472 [2135.51] 2-Point, 3-Point and 4-Point Digital Ground Resistance

Not yet rated Write a review
AEMC
Rp.98.472.600
Availability:
4 - 6 WEEKS
Product Code:
2135.51
Brand:
AEMC
Update Terakhir:
14 Sep 2022
  • Free delivery

  • Money back guarantee

Share

The AEMC Digital Ground Resistance Tester Model 6472 [2135.51] is a portable measurement instrument designed to measure Bond Resistance, Ground Resistance (with and without clamps), Soil Resistivity, Earth Coupling, Step & Touch Potential.

The Model 6472 measures from 0.01 to 99.99kΩ and is auto-ranging, automatically seeking out the optimum measurement range, test frequency and test current. The adjustable test frequency (either manual or automatic) from 40 to 5078Hz test voltage provides rejection of high levels of interference, allowing it to be used under difficult conditions such as the presence of high stray currents that normally affect accuracy. Up to 512 test results can be stored in internal memory for later recall to the display or downloaded to a PC using DataView® software (included) for Automatic Report Generation, Automatic Fall-of-Potential Plot Generation, Frequency/Resistance Plots and much more.

When used in combination with the GroundFlex® Adapter Model 6474 (factory supplied product only), Power Transmission Tower and Tower Leg Ground Resistance testing is also available.

  • Ground Integrity Measurement
  • Ground Resistance testing using the 2 clamp method (no auxiliary rods needed) using optional current probes
  • 2- and 4-Wire Bond Resistance/Continuity Measurement (DC Resistance) with automatic polarity reversal
  • 3-Point Fall-of-Potential measurement with manual or automatic frequency selection
  • 4-Point soil resistivity measurement with automatic calculation of Rho (ρ) and user selection of the Wenner or Schlumberger test method
  • 3-Point Earth coupling measurement
  • Ground Resistance (3-Pole or 4-Pole)
  • Ground Coupling Resistance
  • Selective Resistance
  • Ground Potential
  • Ground Resistance with 2 clamps (no auxiliary rods)
  • Test Voltage 16 or 32V; 41 to 5078Hz
  • Two additional test voltages of 10 and 60 Volts can be manually selected
  • Measures Ground Impedance at frequencies up to 5kHz to test lightning strike protection
  • Manual and automatic frequency scan from 41 to 5078Hz for optimum test accuracy in electrically noisy environments
  • Selectable test voltage of 16 or 32V up to 250mA of test current
  • Auto Power OFF feature
  • Automatic recognition of all electrode connections and their resistance value
  • Stores up to 512 complete test results
  • Display with automatic backlight when entering a function
  • Optically isolated USB communication cable included
  • Automatic report generation including the fall of potential plot
  • Rechargeable NiMH batteries from wall charger or vehicle power
  • Rugged dustproof and rainproof field case - IP53 rated in closed position
  • Includes DataView software for set up, data storage, real-time display, analysis, report generation and system configuration

  • 4-Point Earth Resistance Measurement:
  • Range (Auto-Ranging): 0.011Ω to 99.99kΩ
  • Resolution: 0.001 to 10Ω
  • Accuracy: ±(2% Reading +1ct)
  • Test Voltage: 16 or 32V; 41 to 5078Hz
  • Test Current: Up to 250mA
  • Selective 4-Pole (with optional probes MN82 or SR182):
  • Same characteristics as with 4-point earth resistance measurement
  • 3-Point Earth Resistance Measurement:
  • Range (Auto-Ranging): 0.09Ω to 99.9kΩ
  • Resolution: 0.01 to 100Ω
  • Accuracy: ±(2% Reading +1ct)
  • Test Voltage: 16 or 32V; 41 to 5078Hz 
  • Test Current: Up to 250mA
  • Soil Resistivity 4-Point Measurement:
  • Test method; Wenner or Schlumberger selectable with automatic calculation
  • Range (Auto-Ranging): 0.01 to 99.9kΩ; ρ max: 999kΩm
  • Resolution: 0.01 to 100Ω
  • Accuracy (Typical): ±(2% Reading +1ct)
  • Test Voltage: 16 or 32V; 41 to 128Hz selectable
  • Earth/Ground Potential Measurement V Pot:
  • Range (Auto-Ranging): 0.01mV to 65.00V
  • Resolution: 0.01 to 10mV
  • Accuracy (Typical): ±(5% Reading +1ct)
  • Test Voltage: 16 or 32V; 41 to 5078Hz
  • 2 Clamp Ground Measurement (with optional probes MN82 or SR182):
  • Range (Auto-Ranging): 0.1 to 500Ω
  • Resolution: 0.01 to 1Ω
  • Measurement Frequency: Auto: 1611Hz; Manual: 128Hz-1367Hz-1611Hz-1758Hz
  • DC Resistance Measurement (Bond Testing) 2-Pole (with lead resistance compensation) or 4-Pole (Kelvin sensing):
  • Range (Auto-Ranging): 2-pole: 0.12Ω to 99.9kΩ; 4-pole: 0.020Ω to 99.99kΩ
  • Resolution: 2 -pole: 0.01 to 100Ω; 4-pole: 0.001 to 10Ω
  • Accuracy (Typical): ±(2% Reading +2ct)
  • Test Voltage: 16V DC; (+, - or auto polarity)
  • Test Current: Up to 250mA
  • Current Measurement (with optional probes MN82 or SR182):
  • Range: 0.01mA to 40A, 16 to 400Hz
  • Accuracy (Typical): ±(3% Reading +2ct) typical
  • External Voltage Measurement:
  • Range: 0.1 to 65V AC/DC – DC, 15 to 440Hz
  • Accuracy: ±(2% Reading +1ct)
  • General Features:
  • Pylon Ground Testing: Available by connecting AEMC Model 6474 and a set of GroundFlex sensors
  • Memory:  512 measurements (64KB)
  • Communication: USB 2.0 optically isolated, DataView software included
  • Power Source: 9.6V rechargeable battery pack with external 110/220V charger
  • Battery Life: 1500 tests typical in automatic mode
  • Dimensions: 10.7 x 9.80 x 5.12” (272 x 248 x 130mm)
  • Weight: 7lbs. (3.2kg) with battery
  • Case: UL V0 Polypropylene
  • Operating Temperature: 32° to +113°F (0° to +45°C)
  • Storage Temperature: -40° to 158°F (-40° to +70°C)
  • Relative Humidity: Up to 90%
  • Ingress Protection (IP): IP 53 with cover closed
  • EMC: EN 61326-1
  • Safety Compliance: IEC 61010-1, EN 61557, 50V CAT IV, Pollution Degree 2

  • (1) Carrying bag
  • (1) 110/240V power adapter with US power cord
  • (1) Optical USB cable
  • (1) Rechargeable NiMH battery pack
  • (1) USB stick with DataView software, ground tester workbook and user manual

          Note: Prices are not binding at any time subject to change without prior notice